Features
DMO1140: Thermostat (normally closed),contact breaker for regulating heaters.
DMS1141: Thermostat(normally open), contact maker for regulating of filter fans and heat exchangers or for switching signal devised when temperature limit has been exceeded.
Technical Data | |
---|---|
Temperature switch difference | 7K (±4K tolerance) |
Sensor element | Thermostatic bimetal |
Contact type | Snap-action contact |
Contact resistance | < 10m Ω |
Service life | > 100,000 cycles |
Max . Switching capacity | 250VAC , 10 (2) A 120VAC , 15 (2) A DC 30W |
Connection | 2-pole terminal , clamping torque 0.5 Nm max .: rigid wire 2.5 mm 2 stranded wire ( with wire end ferrule ) 1.5 mm |
Mounting | Clip for 35mm DIN rail,EN60715 or for Cxit filter EF 118 Series |
Casing | Plastic according to UL94 V-0 , light grey |
Dimensions | 60 x 33 x 43 mm |
Weight | Approx . 40g |
Fitting position | Variable |
Operating / Storage temperature | - 20 to +80℃(-4 to +176° F ) /-45 to +80℃(-49 to +176° F ) |
Protection type | IP20 |
*Product Specifications Subject To Changes Without Prior Notice